Backflow Testing in El Segundo, CA
Enforced by El Segundo Fire Department, Fire Prevention Division
El Segundo enforces NFPA 10 with local amendments that go beyond the CA state code. These jurisdiction-specific changes to No El Segundo-specific local amendments to NFPA 10 requirements. Operational permits for facilities storing or using extinguishing agents in quantities triggering CFC permit thresholds are issued by ESFD during annual inspections per ESMC Section 104.1.1. At refinery and aerospace facilities, Class B foam and Class D dry powder extinguishers require the same monthly check cycle plus specialty type-specific verifications. directly affect backflow testing requirements for building owners and property managers in El Segundo.
Compliance Requirements
Annual Backflow Testing
Administrative citation under ESMC Section 1-2-3: $100/$200/$500 per day escalation. West Basin Municipal Water District or Cal Water may suspend water service for non-compliance with backflow prevention requirements.
California Health and Safety Code Section 116800; ESMC Title 13, Chapter 9
View provenance
Code Adoptions
Local Amendments: No El Segundo-specific local amendments to NFPA 10 requirements. Operational permits for facilities storing or using extinguishing agents in quantities triggering CFC permit thresholds are issued by ESFD during annual inspections per ESMC Section 104.1.1. At refinery and aerospace facilities, Class B foam and Class D dry powder extinguishers require the same monthly check cycle plus specialty type-specific verifications.
Local Amendments: ESMC Section 903.3.5.3 (locally added) requires hydraulically calculated fire sprinkler systems not exceed 90% of available water supply capacity — directly affects ITM pressure testing benchmarks and hydraulic design margins. ESMC Section 903.3.9 requires floor control valves and waterflow detection assemblies in buildings 3+ stories or where any floor is 30+ feet above lowest fire department access, creating additional NFPA 25 ITM inspection points. ESMC Section 901.11 and 901.12 require fire watch when fire protection systems fail or produce 2+ activations per week with no confirmed emergency. ITM inspection requests submitted via E-Z Permit Hub.
Local Amendments: ESMC Section 511.3.3 requires smoke detectors connected to NFPA 72-compliant automatic fire alarm system in all mid-rise buildings (4+ stories under 75 feet). ESMC Section 511.3.5 requires fully addressable, electronically supervised fire alarm systems in mid-rise buildings. ESMC Section 903.4.2 requires exterior audible AND visible alarm notification devices on all NFPA 13, 13R, and 13D sprinkler systems — expanding notification beyond base CFC. ESMC Section 510.3 requires permit for ERRCS installation or modification. ESMC Section 510.4.2.9 requires dedicated 2-inch conduit for ERRCS in all new buildings. False alarm cost recovery ordinance (ESMC Chapter 22, Ordinance 1640) tied to monitored NFPA 72 alarm activations.
Local Amendments: No El Segundo-specific amendments to NFPA 96 provisions in ESMC. ESMC Section 308.1.4 deletes CFC Open-Flame Cooking Devices section in its entirety, which may affect outdoor commercial cooking equipment regulation. Kitchen hood suppression system permits require plan check submission through E-Z Permit Hub and ESFD inspection prior to system activation. ESFD Fire Prevention Division inspects all commercial kitchens including The Point development restaurants and aerospace campus cafeterias.
Local Amendments: ESMC Section 903.2 imposes universal sprinkler requirement for all new construction regardless of occupancy — CFC Sections 903.2.1 through 903.2.11.3 deleted in entirety and replaced. Only exception: detached buildings under 1,000 sq ft with Fire Official approval. ESMC Section 511 (Mid-Rise Building life safety package) triggered at 4+ stories under 75 feet — includes pressurized stairways, central control station, emergency voice alarm, standby power for 12 hours minimum, and elevator for fire department use. ESMC Section 903.3.8 prohibits partial sprinkler systems — when any sprinkler requirement applies, full building coverage required. ESMC Section 903.2.22 (Smoky Hollow Specific Plan Area) imposes universal sprinkler and full life safety on all new and substantially renovated buildings within that industrial district.
Authority Having Jurisdiction
Licensed Providers
No listed providers found for this service in El Segundo.
Frequently Asked Questions
How often is backflow testing required in El Segundo?
El Segundo requires backflow testing once per year per California Health and Safety Code Section 116800; ESMC Title 13, Chapter 9. The deadline type is anniversary, with a deadline of 12 months from installation or last test.
Who is the AHJ for backflow testing in El Segundo?
The Authority Having Jurisdiction (AHJ) for backflow testing in El Segundo is the El Segundo Fire Department, Fire Prevention Division. The AHJ reviews inspection reports, issues violations, and has final authority over code interpretation. Contact the fire marshal, Jesse Franco, for questions.
What happens if I miss a backflow testing deadline in El Segundo?
Missing a backflow testing deadline in El Segundo can result in Administrative citation under ESMC Section 1-2-3: $100/$200/$500 per day escalation. West Basin Municipal Water District or Cal Water may suspend water service for non-compliance with backflow prevention requirements. The penalty severity is classified as medium.
What edition of NFPA 10 does El Segundo enforce?
El Segundo enforces the 2022 edition of NFPA 10. This matches the current published edition. Adopted through 2025 California Fire Code (Title 24, Part 9) incorporates NFPA 10 requirements through CFC Section 906. CCR Title 19, Division 1, Chapter 3 (Sections 550-617) maintains California's parallel portable extinguisher regulatory framework independently of the NFPA standard. All extinguisher service work requires a State Fire Marshal-licensed concern per Health and Safety Code Section 13160 et seq..
Data current as of April 2026